DESCRIPTION
NM-B - 12 AWG - 2 Conductor - Copper - With Ground - 1000' Reel
Copper Wire-ROMEX  /  RX122RWG

NM-B-12/2-CU-WG-1000R

COPW RX122RWG 12/2 W/G ROMEX 1000RL 1000 FT REEL TOP 500 ITEM

SE Part Number: 86854

UPC:  98010026306

Part Number: RX122RWG

UNSPSC: 26121614

Status:  STOCK

Country of Origin:  UKN

Your Price:  $325.06 / m
$0.33/ Each
 
Qty  eaAdd to Cart Note: this product is only sold in multiples of 1000 items View Cart Checkout

INVENTORY / AVAILABILITY

Total Availabile: 114320 ea

Availability By Branch

  • Springfield, IL8000 ea
  • Bloomington, IL1000 ea
  • Champaign, IL16000 ea
  • East Peoria, IL1000 ea
  • Danville, IL1000 ea
  • Mt. Vernon, IL4000 ea
  • Mattoon, IL7000 ea
  • Peru, IL1000 ea
  • Rockford, IL1000 ea
  • Decatur, IL3000 ea
  • Moline, IL1000 ea
  • Carbondale, IL5000 ea
  • Davenport, IA6000 ea
  • Edwardsville, IL2000 ea
  • Decatur - CorporateB/O or Special Order
  • East Peoria - CorporateB/O or Special Order
  • Quincy, IL15000 ea
  • Hannibal, MO4086 ea
  • Evansville, IN13234 ea
  • Vincennes, IN20000 ea
  • Terre Haute, IN5000 ea

Compliances

  • UL Standard 83
  • UL Standard 719
  • ASTM B3 and B8
  • NEC Article 334
  • Federal Specification A-A-59544

Outer Jacket

  • Polyvinyl Chloride (PVC)
  • Color-coded: 14 AWG - White; 12 AWG - Yellow; 10 AWG - Orange; 8 AWG - Black; 6 AWG - Black

Applications

  • Residential wiring as branch circuits for outlets, switches, and other loads
  • Exposed or concealed wiring
  • May be run through walls, ceilings and masonry blocks
  • New wiring or replacement wiring
  • Only for use in normally dry locations

Grounding Conductor

  • Bare annealed Copper per ASTM B3 or ASTM B8

Conductor

  • 14 AWG thru 10 AWG bare annealed Solid Copper per ASTM B3
  • 8 AWG and larger stranded bare annealed Copper per ASTM B8
  • Color-coded inners for circuit identification
  • Available with and without ground
  • Rated for 90˚C in dry locations
  • Ampacity is limited to that for 60˚C conductors per NEC Article 334

Insulation

  • Premium-grade Polyvinyl Chloride (PVC) with a Nylon jacket
  • Color-coded: 2 conductor - Black, White; 3 conductor - Black, White, Red

Assembly

  • Type THHN inners, rated 90˚C in dry locations
  • 2-conductor - insulated conductors laid parallel with a Bare Copper grounding conductor wrapped in paper and laid parallel between the insulated conductors
  • 3-conductor - insulated conductors laid parallel or twisted together with Bare Copper grounding conductor wrapped in paper
  • The entire assembly is wrapped with a paper separator prior to applying the Polyvinyl Chloride (PVC) outer jacket

Packaging

  • 250' or 125' coils or 1000' reels
  • Length: 1000'
  • Conductor Size: 12/2G AWG
  • Conductor Size: 3.31 mm2
  • Conductor Material: Copper
  • Number of Wires: Solid
  • Insulation Thickness (in): 0.015
  • Insulation Thickness (mm): 0.38
  • Insulation Material: PVC
  • Insulation Color: Yellow
  • Jacket Thickness (in): 0.004
  • Jacket Thickness (mm): 0.1
  • Nominal Cable O.D. (in): .160 x .450
  • Nominal Cable O.D. (mm): 4.064 x 11.430
  • Copper Weight (lbs/1000 FT): 60
  • Copper Weight (kg/km): 90
  • Total Weight (lbs/1000 FT): 82
  • Total Weight (kg/km): 122
  • Ampacity: 20
  • Wet Location Use: No
  • Direct Burial: No
  • Grounded: Yes
  • Stranding: Solid
  • Voltage Rating: 600 V
 
 
Time Zone 
 

Alternative Product Disclaimer

The online Cross-Reference Information presented on Springfield Electric's Website is proprietary and provided as a tool to determine potential equivalent catalog numbers. Catalog numbers of other manufacturers are shown for products that appear to be equivalent in their functional use, though not necessarily interchangeable. Product replacements/cross-reference may not be exact one-for-one match. They may not be equivalent as to form-fit-function requirements and may require a system replacement . Springfield Electric and the manufacturers recommend review of manufacturers' product literature, associated documentation of product details and verification of the information necessary to make the appropriate product selecting for a given application.